G5DFR Multi-Functional Digital Fault Recorder
The BlackBox G5DFR is a fully featured digital fault recorder equipped with PQZIP technology. The G5DFR is a distributed multi-functional data acquisition device that continuously records all waveform signals at sampling rate of 1,024 samples per cycle.
PQZIP inside
- Continuous waveform recording
- Trigger free setup
- 5,000 power parameters @ 1/2 cycle resolution
- Easy deployment
Superior Accuracy
The G5DFR is equipped with 24 bit ADC to yield, a superior accuracy far surpassing IEC 61000-4-30 Class A requirements, thereby capturing the finest details
& deviations in PQ parameters.
Class A
Far surpassing the highest standards set by the industry, the BLACKBOX device series complies with standards for: aggregations, time clock uncertainty, flagging, and transient influence quantities.
Synched Monitoring
The BLACKBox DFR’s synchronisation algorithm is based on several sources with an automatic hierarchy for the preferred source availability (accuracy based hierarchy). This unique time synchronisation algorithm assures that logged data from multiple units is synchronised & displayed on the same time scale with typical 1 μs resolution.
Multi-functional Recorder
- Digital Fault Recorder (DFR)
- Phasor Measurement Unit (PMU)
- Power Quality Monitoring (PQM)
- Sequence of Event Recording (SER)
- Dynamic System Monitoring (DSM)
- Impedance based Fault Location (IbFL)
- Energy Billing Measurement (EBM)
- Impedance Distance to Fault Location (IDFL)
Unique Features
- 24-Bit Continuous acquisition at 1,024 sample per cycle[50/60Hz]
- Modular Design
- Centralized and decentralized architecture
- Supreme synchronization
- Complies with IEC 61850 MMS, GOOSE messaging and sample value
- Comprehensive web interface
- 7” touch LCD
- Scalable architecture
Continuous Waveform Recordings
The G5DFR is a multi-functional recorder able to record and store all electrical waveform at any given time, for more than a year, with no gaps in the data. RMS, harmonics and any other values from waveform in post-processing are calculated, including the tabulation of more than 10,000 parameters.
Compliance & Custom Reporting
The G5DFR in conjunction with PQSCADA Sapphire software offers a comprehensive reporting and compliance engine which is able to produce and schedule compliance reports in (printable in .pdf format) to multiple electrical standard’s including IEEE519 2014, IEEE519 2022, EN50160. It also allows for the design of custom report templates meeting the users specific and individual reporting requirements. Reports can be generated manually or on a daily, weekly, monthly or yearly schedule. Reports can also be triggered by compliance policy violation or by event occurrence.
Report Sample
Supreme Trends Resolution
The G5DFR measures and records 5,000 power parameters continuously at a resolution of ½ cycles, 10/12 cycles, 150/180 cycles, 10 min and 2 hours of which, any given resolution is calculated for display and reporting purposes. Hence, there is no need to select which parameters to log, and more importantly, which parameters to ignore.
POWER QUALITY MANAGMENT SOLUTION
In conjunction with PQSCADA Sapphire software, have real time overview and complete control of your power network whether you are an energy provider or the end user. PQSCADA Sapphire is a multi-component, vendor free, Power Quality software which integrates data from all existing protection relays, fault recorders, power quality analyzers, smart meters and other data sources into a single data base. Set autonomous thresholds for alerts, fault location, outages and power quality incidents using preset or custom parameters.
Harmonics & Inter-Harmonics Analysis
The G5DFR power quality analyzer boosts two FFT engines for harmonics analysis: Cycle by Cycle: performs FFT at 1 cycle resolution for extended bandwidth. This engine provides 512 harmonics order at 50Hz resolution. 10/12 Cycles: performs FFT 10/12 cycles resolution for extended resolution and sub-grouping calculation. This engine provides the magnitude and angle of 512 spectrum components at 5Hz resolution.
COMPREHENSIVE EVENT MECHANISM
The G5DFR analyser is designed to detect any event occurring on your system. The event mechanism allows you to configure events on any measured parameter (more than 1,000) and/or I/O ports. The event mechanism supports out-of-limit events as well as rate of changed limits. The G5DFR records the waveform signals continuously. The event configuration doesn’t trigger the recording but rather stores summary logs including start and end time, duration, severity and magnitude of the event. All events are displayed in a tabular or scatter charts as CBEME/ITIC.
Phasor Measurement Unit
Complies with the most updated standard for synchrophasor measurements of power systems IEEE C37.118-2011, including the amendment IEEE C37.118.1a-2014. IEC/IEEE 60255-118-1-2018 Certified. Two independent synchrophasor data streams enable to report a synchrophasor data with two different report-rates and/or different performance classes (P/M) and/or data type simultaneously. Ultra-fast report rate for both P & M classes:
Performance Class | Max report rate for 50Hz | Max report rate for 60Hz |
---|---|---|
P | 200/sec | 240/sec |
M | 100/sec | 120/sec |
Support for simultaneous synchrophasor data stream over TCP/IP and UDP/IP. It can be configured for unicast or multicast, enabling a better design of WAMS communication and suitable for WAMS with several utilities or applications involved.
SPECIFICATIONS
Data Acquisition |
|
---|---|
Sampling Rate, Maximum Samples/Cycle | 256/512/1,024 |
Digital & Aux Channels Sampling Rate Samples/Cycle | 128 |
Type of Analog to Digital Converter | 24 Bit |
Mechanical |
|
Dimensions [W X H X D] | 21.5 x 22.1 x 29.1 cm (8.48” x 8.7” x 11.45”) |
Frequency Measurement |
|
Fundamental Frequency | 37 – 70Hz |
Frequency Resolution | 1mHz |
Frequency accuracy | ±1mHz |
Phasor Measurement Unit / Synchrophasor |
|
Applicable Standard | IEEE C37.118 – 2011/2014 |
M Class transmission Max rate | 100/sec for 50Hz, 120/sec for 60Hz |
P Class Transmission rate | 200/sec for 50Hz, 240/sec for 60Hz |
Communication ports (Rear Panel ) |
|
SFP Ports (100/1,000MB/s) | 2 |
Serial Ports | 1 |
USB PORTS | 2 |
PPS | 1 |
Communication ports (Front Panel ) |
|
USB PORTS | 2 |
Ethernet Port (10/100MB/s) | 1 |
Serial | 1 |
Communication Protocols |
|
IEC 61850 | MMS, GOOSE, Sample Value |
MODBUS | TCP/IP, RTU |
Power Supply |
|
Main | 100 – 260 VAC @50/60 Hz or 100-300 VDC |
Aux | 24VDC |
Time Synchronization |
|
Internal Real Time Clock | 20PPM |
GPS | 0.5μsec |
IRIG B | 0.5 μsec |
NTP | 100 μsec |
Environmental Conditions |
|
Operation Temperature | -20C to 70C (-40F to 1580F) |
Storage Temperature | -40C to 85C (-40F to 185F) |
Human Machine Interface |
|
Built in 7” 1MP LCD. Additional comprehensive web server for local and remote real-time monitoring, historical data analysis and control. |